Henan Huatai Special Cable Co., Ltd.

PVC insulated yellow and green wire

PVC insulated yellow and green wire
Product Detailed

1 19-years experience
2 VDE,UL,CCC,ROHS,CE certificate
3 Free Samples
4 Professional QC inspection
5 factory direct sale

1 Standard

GB 5023.11997 , JB 8734.15-1998, Q/ZEL 02-2002, GB 5023.17-1997,  IEC227

2 Voltages U0/U:  

450/750V300/500V300/300V.(600/1000V also available)

Max. permissible continuous operating temperature of the conductor: 70
The ambient temperature under installation should not below 0.

Impedance (ohms): 100±2ohm

 

3 Application

The products is suitable for use in power installations, fixed wiring or flexible

connections for electrical appliances like lighting, electronic equipment, instrument 

and communication equipment with rated voltage 450/750V or less

4 Model and Name

Model

Name

BV

Copper Core PVC Insulation Wire

BLV

Aluminum Core PVC Insulation Wire

BVR

Copper Core PVC Insulation Flexible Wire

BVV

Copper Core PVC Insulation PVC Sheath Round Wire

BVVB

Copper Core PVC Insulation PVC Sheath Flat Wire

BLVVB

Aluminum Core PVC Insulation PVC Sheath Flat Wire

BV-90

Copper Core Heat-resistance 105oC PVC Insulation

 

5 Specification Size and Technical Data

 Commen wire

 

Nominal
sectional area
mm2
Conductor
No/Dia.
mm
Nominal
Insulated thick
mm
Max overall
Dia.
mm
Condcutor
Resistance at
20
Min insulated
resistance at
70MΩ/km
Weight
Kg/km
CuAlCuAl
1.51/1.380.73.312.1-0.01119.2-
1.57/0.520.73.512.1-0.01020.6-
2.51/1.780.83.97.4111.80.01030.815.0
41/2.250.84.44.617.390.008545.521.0
61/2.760.84.93.084.910.007065.029.0
107/1.351.07.01.833.080.0065110.052.0
167/1.701.08.01.151.910.0050170.070.0
257/2.141.210.00.7271.200.0050270.0110.0
357/2.521.211.50.5240.8680.0040364.0150.0
5019/1.781.413.00.3870.6410.0045500.0200.0
7019/2.141.415.00.2680.4430.0035688.0269.0
9519/2.521.617.50.1930.3200.0035953.0360.0
12037/2.031.619.00.1530.2530.00321168.0449.0
15037/2.251.821.00.1240.2060.00321466.0551.0
18537/2.522.032.50.0990.1640.00321808.0668.0

 

 Flexible wire

 

 

Nominal
sectional area
mm2
Conductor
No/Dia.
mm
Nominal
Insulated thick
mm
Max overall
Dia.
mm
Condcutor
Resistance at
20
Min insulated
resistance at
70MΩ/km
Weight
Kg/km
2.59/0.410.84.27.410.01133.0
419/0.520.84.84.610.00948.0
619/0.640.85.63.080.008468.0
1049/0.521.07.61.830.0072115.0
1649/0.641.08.81.150.0062176.0
2598/0.581.211.00.7270.0058272.0
35133/0.581.212.50.5240.0052384.0
50133/0.681.416.50.3870.0051510.0
70189/0.681.416.50.2680.0045714.0
95259/0.681.19.50.1390.0035965.0
120259/0.761.822.00.1530.00321210.0
150259/0.851.825.00.1240.00321510.0

6 Coming to our factory

 