Control Cable for Mining use
Product Detailed
Application
Cables are applicable to transmit electric energy for colliery equipments with A.C rated voltage up to 10kV.
Main technological indexes:
1. DC resistance of conductor at 200C shall comply with GB/T3956.
2. XLPE: cables with rated voltage U0 above 1.8kV shall with stand partial discharge test; the magnitude of the discharge at 1.5U0 shall not exceed 20Pc.
PVC: cables with rated voltage U0 above 3.6kV shall be carried out partial discharge test; the magnitude of the discharge at 1.5 U0 shall not exceed 40pC.
3. Cables with rated voltage up to 3.6kv shall withstand 2.5 U0 +2kV voltage test; cables with rated voltage above 3.6kv shall withstand 2.5 U0 voltage test.