Henan Huatai Special Cable Co., Ltd.

silicone rubber control cable

silicone rubber control cable
Product Detailed

Silicon Rubber Control Cable (flame retardant)
Tinned Copper Conductor
UO/U: 450/750V
-60 C~+180C
Silicone rubber insulation

(flame retardant) Silicon RubberControl soft Cable

It is widely used for supervising and controlling return circuit of rated voltage 450/750V or lower for production under high temperature in the fi eld of steel & iron, refi nery, power plant, coking plant, aviation, metallurgy, machinery, petrochemical industry etc. It has good feature of high temperature resistance, fl ame retardance, radiation resistance, aging resistance, ozone resistance, water proof, freezing resistance and weather resistance.

I.                   Working Condition

1: A.C rated voltage UO/U: 450/750V

2: Temperature for installing is no lower than -20°C.

3: Working temperature allowed by cable is -60°C~+180°C. Recommended bending radius is no less than 6 times that of cable OD and 10 times that of cable OD for cable with copper tape shielding.

4: It has good features of ozone aging resistance, thermal aging resistance, ultraviolet resistance and atmosphere aging resistance.

5: Good performance of electric insulation, corona resistance and arc resistance.

 II. Type, description and main application occasion listed in the following table 1 

Table 1

Type

Description

Main application occasion

(ZR)-KGG

Control cable with Cu core, silicon rubber insulation and sheath

To be fixedly laid indoor, in cable furrow or pipe

(ZR)-KGGP

Control cable with Cu core, silicon rubber insulation and sheath, braided shielding

To be fixedly laid indoor, in cable furrow or pipe with demand on shielding

(ZR)-KGGP

2

Control cable with Cu core, silicon rubber insulation and sheath, copper tape shielding

To be fixed laid indoor, in cable furrow or pipe with demand on shielding

(ZR)-KGGR

Control soft cable with Cu core, silicon rubber insulation and sheath

To be laid indoor or in the environment with demand on softness and mobility

(ZR)-KGGRP

Control soft cable with Cu core, silicon rubber insulation and sheath, braided shielding

to be laid indoor or in the environment with demand on softness and shielding

IV.     Technical Parameter

1: Insulated resistance of finished cable insulated conductor will be no less than 50M under the condition

that cable length is 1km and temperature is 20°C.

2: Finished cable shall bear AC voltage test of 3kV under power frequency for 5 minutes without puncture of insulation.

 Table 3

(mm2) Nominal cross section area

Conductor structure   Pieces/diameter   (mm)

Conductor DC resistance at 20°C                       (Ω/km)

Voltage withstand stress

Non tinned

tinned

0.5

1/0.8

36

36.7

3kV/5min  Insulation    without puncture

7/0.30

36

36.7

16/0.20

39

40.1

0.75

1/0.97

24.5

24.8

7/0.37

24.5

24.8

24/0.20

26

26.7

1

1/1.13

18.1

18.2

7/0.43

18.1

18.2

32/0.20

19.5

20

1.5

1/1.38

12.1

12.2

7/0.52

12.1

12.2

30/0.25

13.3

13.7

2.5

1/1.78

7.41

7.56

7/0.68

7.41

7.56

49/0.26

7.98

8.21

4

1/2.25

4.61

4.7

7/0.85

4.61

4.7

56/0.30

4.95

5.09

6

1/2.76

3.08

3.11

7/1.04

3.08

3.11

84/0.30

3.3

3.39

10

7/1.35

1.83

1.84

 

 

 



Copyright Notice @ 2008-2022 B2BAGE Limited and/or its subsidiaries and licensors. All rights reserved.