Henan Huatai Special Cable Co., Ltd.

Duplex Aluminum Service Drop Cable

Duplex Aluminum Service Drop Cable
Product Detailed

Service Drop Cable for Power tranmission, used for rebuilding of urban and forest regions.

Applications:

To supply 120 volt aerial service for temporary service at construction sites, outdoor or street lighting. For service at 600 volts or lower at a conductor temperature of 75°C maximum.

 

Construction:

Concentric strand or compressed 1350-H19 conductor, polyethylene or crosslinked polyethylene insulation, concentric strand AAC, ACSR, or 6201 alloy neutral messenger.

 

Standards:

B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.

B-231 Aluminum Conductors, Concentric-Lay-Stranded.

B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).

B-399 Concentric-Lay_Stranded 6201-T81 Aluminum Alloy Conductors.

B498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).

Duplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-474.

Code

Word

Phase Conductor

Bare Neutral Messenger

Weight Per 1000 ft. (lbs.)

Allowable Ampacity+

Size (AWG)

Strand- ing

Insul. Thick. (mils)

Size (AWG)

Strand- ing

Rated Strength (lbs.)

XLP

POLY

XLP

POLY

AAC NEUTRAL-MESSENGER

Pekingese

6

1

45

6

7

563

61

61

85

70

Collie

6

7

45

6

7

563

64

64

85

70

Dachshund

4

1

45

4

7

881

92

92

115

90

Spaniel

4

7

45

4

7

881

96

96

115

90

Doberman

2

7

45

2

7

1350

147

147

150

120

Malemute

1/0

9

60

1/0

7

1990

234

234

205

160

* Code Words For XLP Insulated Products Are Formed By Adding "/XLP" to the Conventional Code Words Above (e.g.-Chihuahua/XLP).+ Conductor Temperature of 90°C For XLP, 75°C For Poly; Ambient Temperature of 40°C; Emissivity 0.9; 2 ft./sec. Wind In Sun.

 

Code Word

Phase Conductor

Bare Neutral Messenger

Weight Per 1000 ft. (lbs.)

Allowable Ampacity

Size (AWG)

Strand- ing

Insul. Thick. (mils)

Size (AWG)

Strand- ing

Rated Strength (lbs.)

XLP

POLY

XLP

POLY

ACSR NEUTRAL-MESSENGER

Setter

6

1

45

6

6/1

1190

72

72

85

70

Shepherd

6

7

45

6

6/1

1190

75

75

85

70

Eskimo

4

1

45

4

6/1

1860

110

110

115

90

Terrier

4

7

45

4

6/1

1860

115

115

115

90

Chow

2

7

45

2

6/1

2850

176

176

150

120

Bull

1/0

9

60

1/0

6/1

4380

280

280

205

160

* Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Chihuahua/XLP).+ Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.

 



Copyright Notice @ 2008-2022 B2BAGE Limited and/or its subsidiaries and licensors. All rights reserved.