Henan Huatai Special Cable Co., Ltd.

Electric cable Overhead ABC cable

Electric cable  Overhead ABC cable
Product Detailed

RATED VOLTAGE 0.6/1KV / ALUMINIUM CONDUCTOR OR ALUMINIUM ALLOY CONDUCTOR/ sPVC OR PE OR XLPE INSULATION AERIAL BUNDLE CABLES

Aerial Busndled Cables : RATED VOLTAGE 0.6/1KV /  ALUMINwIUM CONDUCTOR OR ALUMINIUM ALLOY CONDUCTOR/  sPVC OR PE OR XLPE INSULATION AERIAL BUNDLE CABLES.

 DESCRIPTION
The aerial bundle cables designed for overhead distribution lines have an insulated neutral
rnessenger
rnade of AAAC, which the insulated alurniniurn phase conductors are helically wound over it. Cables
are rated at 0.6/1(1.2) kV and conforrn to IEC 60502
The rnain advantages of aerial bundle cables include :
1. Ease of erection and stringing
2. Practically no tree - trirnrning required
3. Less rnaintenance 

 

CONSTRUCTION

1   Phase conductor :
 The phase conductors shall be of H68 Condition aluminium conductor and compacted circular
stranded.

2   Messenger conductor :
The neutral messenger conductor shall be of aluminium alloy conductor and compacted circular
stranded.

3   Street Lighting conductor :
The street lighting conductors shall be of H68 Condition aluminium conductor and compacted circular
stranded.

4   Insulation :
The phase, messenger and street lighting conductors shall be extruded with Polyethylene ( PE ) as
insulation.

5   The Completed Cable
The cable consists of insulated phase and  street lighting aluminium conductors, shall be held
firmly onto the
insulated neutral messenger aluminium alloy conductor in a right-hand ( Z ) direction of lay.

Cond. SizeMaximum DiameterThickness of insulation
Approx. Diameter
Approx. WeightDC resistance
Permissible current DMin.breaking strength
Phase coreNeutral corePhase coreNeutral corePhase core
Neutral core
Phase core
Neutral core
mm2mmmmmmmmmmKg/km/km/kmAkNkN
2x50 + 508,4                  9,51,5                1,5265900,641                0,651507,0                16,6
3x50 + 508,4                  9,51,5                1,5297850,641                0,651507,0                16,6
3x70 + 5010,1                9,51,5                1,5328950,443                0,651859,8                16,6
3x95 + 7011,9                10,71,7                1,53612100,320               0,50822513,3               20,5
3x120 + 7013,5                10,71,7                1,53814300,253               0,50826016,8               20,5
3x150 + 7014,9                10,71,7                1,54116650,206               0,50828521,0               20,5

 

Cond. Size
No. of core
Maximum Diameter
Number of wireThickness of insulation
Approx. massDC Resistance at 20CMin. Breaking strength
Conductor
Insulated coreCable dia.
mm2 mmmmmmNo.mmKg/kmohm/kmkN
102
3
4
3,756,613.2
14.3
16
713215
325
430
1837,4
11,1
14,8
162
3
4
4,657,515
16.2
18.2
713325
490
655
11512,0
18,0
24,0
252
3
4
5,98,717.4
18.8
21.1
713500
750
995
72718,8
28,2
37,6
352
3
4
7,09,819.6
21.2
23.7
713675
1015
1355
52426,4
39,6
52,8

 

  



Copyright Notice @ 2008-2022 B2BAGE Limited and/or its subsidiaries and licensors. All rights reserved.